HOME > Products > Instrument Transformer Testing
CTP-200P CT/PT Analyzer
Revolutionary testing solution for testing various CTs and PTs

CT/PT Analyzer CTP-200P is capable of testing Protection CTs, Measuring CTs, TP class CTs and inductive PTs according to IEC61869-2(IEC60044-1,60044-6), IEC61869-3(IEC60044-2), IEEE/ANSI C57.13 etc. test standards. It allows to test the knee-point voltage up to 40kV CTs and PTs on-site in power grids or in manufacturers' production facilities or test labs.

+86 186 8208 3519 sales@haomaitest.com
  • Descriptions
  • Specifications
  • Download
  • Video
Descriptions

The CT/PT Analyzer CTP-200P is the revolutionary testing system for various CTs and PTs according to IEC and IEEE/ANSI standard. The Analyzer can automatically complete the test within seconds by one click of the patented multifunctional rotary mouse. It allows to test the knee-point voltage up to 40kV CTs and PTs on-site in power grids or in manufacturers' production facilities or test labs.

The main features of CT/PT Analyzer CTP-200P are as follows:

●Able to test Protection CTs, Measuring CTs, TP class CTs and inductive PTs

●Test excitation characteristic and error curve based on low-frequency measurement principle 

●Measure ratio, polarity, ratio error and phase displacement error based on voltage method

●Adopt patented multifunctional rotary mouse to replace the keypad 

●Adopt 5.7 inches LCD screen for display

●Adopt DSP, ARM and embedded LINUX operation system

●Both local test and PC remote test available

●Higher measurement accuracy: 0.05 %

●Print test results directly by built-in thermal printer

●Small and light weight (9kg / 19.84 lbs) for easy transport

Specifications

●Test Standard: IEC61869-2(IEC60044-1,60044-6), IEC61869-3(IEC60044-2), IEEE/ANSI C57.13

●Maximum Knee Voltage Measurement: 40kV

●Output Range:

voltage: 0~180V(RMS)

current: 0~12A(RMS), 36A(peak value)

●Voltage Measurement Accuracy: ±0.05%

●CT Ratio Measurement:  

range:1~30000

accuracy: ±0.05%

●PT Ratio Measurement:

range:1~10000

accuracy: ±0.05%

●Phase Measurement:

accuracy: ±2min

resolution: 0.01min

●Secondary Winding Resistance Measurement:

range: 0~300Ω

accuracy: 0.1%±1mΩ

●Burden Measurement:

range: 0~300VA

accuracy: 0.1%±0.1VA

●Memory Capacity: >3000 groups test results

●Power Supply

Nominal input voltage

customized (AC230V/120V±10%, 1-phase)

Nominal frequency

50/60 Hz

Rated current

10A at 230V / 12A at 120V

Connection

standard AC socket (IEC 60320)

 

●Environmental Conditions

Operation temperature

0 ... +50 °C (+32 ... +122 °F)

Storage temperature

-25 ... +70 °C (-13 ... +158 °F)

Humidity range

relative humidity 5 ... 95 %, non-condensing

Vibration

IEC 60068-2-6(20m/s2 at 10 ... 150 Hz)

 

●Miscellaneous

Weight

9kg(19.84 lbs)

Dimensions (W x H x D, without handle)

340×300×150mm(13.39x11.81x5.91 in)

Connection port

2 USB2.0 ports, 1 communication port

 

●Safety Standards, Electromagnetic Compatibility

EMC

The product adheres to the electromagnetic compatibility (EMC) Directive 2004/108/EC(CE conform)

IEC 61326-1; IEC 61000-6-4; IEC 61000-3-2/3

Safety

The product adheres to the low voltage Directive 2006/95/EC(CE conform).

IEC 61010-1

 

CT/PT Analyzer CTP-200P is the best choice for testing Current Transformers and Potential Transformers(Voltage Transformers).

Copyright © 2020 HAOMAI ELECTRIC TEST EQUIPMENT CO.,LTD All rights Reserved.